HP Insight Remote Support 7.0.9 Monitored Devices Configuration Guide

Chapter 34: Configuring Uninterruptable Power
Supplies
Uninterruptable Power Systems (UPS) come with either a Management Module or a Network Module
installed, depending on the model. Use the appropriate configuration procedure below for your model:
l To configure a UPSthat uses a Management Module, see "Configuring UPS Management Modules"
below.
l To configure a UPSthat uses a Network Module, see "Configuring UPS Network Modules" on page
249.
Configuring UPS Management Modules
The Uninterruptable Power Systems (UPS) Management Module is an option in several HP Rack-
Mountable and Tower UPS units, and these units can be monitored by Insight Remote Support through the
module.
Important: Configuration collections are not supported.
Fulfill Configuration Requirements
To configure your UPS Management Modules to be monitored by Insight RS, complete the following
steps:
Task Complete?
Make sure Insight RS supports your UPS Management Module by checking the HP
Insight Remote Support Release Notes.
Configure SNMP on the UPS Management Module and set the Hosting Device as a trap
receiver.
Add the SNMP protocol to the Insight RS Console.
Discover the UPS Management Module in the Insight RS Console.
Send a test event to verify connectivity between your UPS Management Module and
Insight RS.
Table 34.1 UPS Management Module Configuration Steps
Install and Configure Communication Software on
Management Modules
To configure your monitored devices, complete the following sections:
Configure SNMP
SNMP can be setup in the SNMP Traps screen in the UPS Management Module web interface.
Page 247 of 267HP Insight Remote Support 7.0.9:Monitored Devices Configuration Guide