Integration for Tivoli

Appendix B: HP SNMP events 102
Tivoli types TEC class Description TEC priority
cpqRPMTrapUPSLossOfRedunda
ncyCleared (21024)
IM_21024 This event occurs when a UPS device is
reporting a loss of redundancy cleared or
configuration has changed from N+1 to
Capacity.
Harmless
cpqRPMTrapUPSOnBuck
(21029)
IM_21029 This event occurs when a UPS device is
reporting an On Buck condition.
Warning
cpqRPMTrapUPSOnBoost
(21031)
IM_21031 This event occurs when a UPS device is
reporting an On Boost condition.
Warning
cpqRPMTrapUPSManualLoadDu
mped (21033)
IM_21033 This event occurs when the UPS has been
powered off with user interaction.
Critical
cpqRPMTrapUPSManualLoadDu
mpedCleared (21034)
IM_21034 This event occurs when a UPS device is
reporting UPS output has been restored.
Harmless
cpqRPMTrapUPSFanFailure
(21035)
IM_21035 This event occurs when a UPS device is
reporting a fan failure has occurred.
Fatal
cpqRPMTrapUPSFanFailureClear
ed (21036)
IM_21036 This event occurs when a UPS device is
reporting a fan failure has been cleared.
Harmless
cpqRPMTrapUPSEPOInitiated
(21037)
IM_21037 This event occurs when a UPS device is
reporting an Emergency Power Off (EPO)
command has been received to shutdown
the UPS immediately with out delay. This
command may come from a local control
panel or from a remote source.
Fatal
cpqRPMTrapUPSCheckBreaker
(21041)
IM_21041 This event occurs when a UPS device is
reporting an output Breaker or Relay has
failed or may be stuck open or closed with
this alarm.
Critical
cpqRPMTrapUPSCheckBreakerCl
eared (21042)
IM_21042 This event occurs when a UPS device is
reporting all Breakers are functioning
normally.
Harmless
cpqRPMTrapUPSCabinetDoorOp
en (21045)
IM_21045 This event occurs when a UPS device is
reporting a cover panel has been removed
while utility power is present.
Fatal
cpqRPMTrapUPSCabinetDoorOp
enCleared (21046)
IM_21046 This event occurs when a UPS device is
reporting a cover panel has been replaced.
Harmless
cpqRPMtrapUPSBypassOnAuto
(21047)
IM_21047 This event occurs when a UPS device is
operating in auto bypass mode.
Critical
cpqRPMtrapUPSBypassOnAutoC
leared (21048)
IM_21048 This event occurs when a UPS device is
reporting it is no longer on auto bypass.
Harmless
cpqRPMTrapUPSBatteriesDiscon
nected (21053)
IM_21053 This event occurs when a UPS device is
reporting batteries are not connected to the
UPS.
Critical
cpqRPMTrapUPSBatteriesDiscon
nectedCleared (21054)
IM_21054 This event occurs when a UPS device is
reporting all UPS batteries have been
reconnected.
Harmless
cpqRPMTrapUPSBatteryLow
(21055)
IM_21055 This event occurs when a UPS device is
reporting low battery.
Fatal
cpqRPMTrapUPSBatteryLowClea
red (21056)
IM_21056 This event occurs when a UPS device is
reporting low battery has been cleared.
Harmless
cpqRPMTrapUPSBatteryDischarg
ed (21057)
IM_21057 This event occurs when a UPS device is
reporting batteries are completely
discharged.
Critical