HSG60 and HSG80 Controller and HSx80 Cache Module Replacement Procedures for Array Controller Software V8.7x-x Release Notes

Replacing HSG60 and HSG80 Controllers in Single and Dual-Redundant Controller Configurations
25HP StorageWorks HSG60 and HSG80 Controller and HSx80 Cache Module Replacement
Procedures for Array Controller Software V8.7x-x Release Notes
5. For the controller to be replaced, complete the following substeps:
Caution: Use thin needle-nose pliers to remove the cable from the controller
without potentially damaging the cable for fiber optic cables without extender
clips.
a. Disconnect all host bus cables from the controller being removed.
b. Disengage both controller retaining levers, and remove the controller
from the enclosure (see Figure 7 on page 17).
c. Place the controller in an antistatic bag or on a grounded antistatic mat.
6. For the operational controller, complete the following substeps:
a. Observe that after the “other controller” is removed that FRUTIL restarts
all device ports and asks if a replacement controller is available.
b. Enter N(o) after FRUTIL asks you if a replacement controller is available,
and disconnect the PC or terminal from the controller maintenance port.
FRUTIL exits. If you have a replacement controller available, complete
the instructions inInstalling an HSG60 or HSG80 Controller in
Dual-Redundant Controller Configurations.”
Caution: If reverting to a single-controller configuration, fill the vacant
controller bay with a blank bezel to prevent the enclosure from developing an
over-temperature condition.