Insight Environmental Configuration User Guide
Creating a project 56
6.
Select the new Modbus Integrator object to configure the properties for the power meter.
a. Edit the Modbus Name to reflect the power meter you are configuring.
b. Edit the Modbus ID and Register so that the power variable can be extracted for PUE calculation.
The Register should be equal to the total active power (kW) for the power meter. For more
information, see the documentation from the power meter manufacturer.