HP StorageWorks Enterprise Modular Library E-Series user guide (AH876-96001, October 2007)

10445
1
1
Library main power switch
Figure 23 Library main power switch control
NOTE:
The following step applies only when the library is powered on for the rst time or when a
new interface controller is installed. This step is necessary to put the interface controller
into managed mode.
3. If this is the rst time the library has been powered on after delivery, or if a new interface controller
was installed, congure the interface controller so that it is recognized by the Interface Manager
card. Do one of the following:
If your library has an e2400-FC 2Gb interface controller, wait approximately t wo minutes,
and turn off the main power switch. Wait several seconds and then turn on the power
switch again.
If your library has an e 2400-FC 4Gb interface controller, reset the interface controller twice.
To reset the interface controller, insert a paper clip into the reset hole. After resetting the
interface co ntroller, wait three minutes, then reset it again.
NOTE:
A 71e library requires approximately 15 minutes to initialize. All other library models
require up to an hour to initialize and do an inventory. Nothing displays on the OCP for
the rstfewminutesofthisprocess.
Powering off the library
1. Use y
our backup software to stop all library activity and make sure the picker is empty.
2. On the OCP, select the Operations > Unlock Door command to park the robot.
3.
After the robot is parked, press the main power switch (Figure 23 on page 40) to the O (Off) position.
40
Using the library