Site Preparation Guide, Second Edition - HP Carrier Grade Blade Server bh3710

Appendix A
System Specifications and Requirements
38
Power Supply 750.0 Watts
a. These wattage values are used to perform the
calculations in Table A-3, “Power Consumption and
Air Conditioning Requirement Summary.”
Table A-3 Power Consumption and Air Conditioning Requirement Summary
Component Quantity
Multiply Qty.
by VA Value
Power
Dissipated
Air
Conditioning
Required
Chassis 1 0.0 Watts 0
HP Server bp2200 1 89.0 Watts 89.0 Watts 304 Btu
FC Storage Blade 1 to 2 35.1 Watts 70.2 Watts 240 Btu
Management Blade 1 18.6 Watts 18.6 Watts 64 Btu
Management LAN Blade 2 7.0 Watts 14.0 Watts 48 Btu
Power Supply
2
a
84.0 Watts 287 Btu
Total 276 Watts 943 Btu
a. Maximum power dissipated with 1 or 2 power supplies is 84 Watts.
Table A-4 System Power Consumption
Power Consumption Description
3.72A @ 72 Volts DC
Theoretical maximum power consumption
a
a. See glossary for definition.
Table A-2 Power Consumption (Maximum) (Continued)
Power Required
VA
a