HP DC04 SAN Director Switch Hardware Reference Guide
Table 11 (page 61) describes the core switch blade LED patterns and the recommended actions
for those patterns.
Table 11 CR4S-8 blade LED descriptions
Recommended actionStatusColorLED purpose
No action requiredCP blade has valid power.Steady greenPower
Ensure blade is firmly seated
and has power.
CP blade does not have
incoming power.
No light (LED is off)
Verify that the power LED is on.CP blade is either healthy or
does not have power.
No light (LED is off)Status
Ensure blade is firmly seated
and switch has completed
booting. If LED remains amber,
CP blade is faulty or the switch
is still booting.
Steady amber
contact HP. Blade may not be
compatible with other blades in
the chassis. See “DC SAN
Director 10/24 FCoE blade
(FCOE10-24) overview” (page
117) for limitations.
Pull blade out and reseat it. If
LED continues to flash, replace
blade.
CP blade is not seated correctly
or is faulty.
Slow-flashing amber (on
2 seconds; then off 2
seconds)
Find out-of-bounds environmental
condition and correct it.
Environmental range exceeded.Fast-flashing amber (on
1/2 second; then off
1/2 second)
Ensure ICL cable is correctly
installed.
No ICL or ICL cable present, but
no connection.
No light (LED is off)LINK LED
No action requiredICL connectedSteady green
No action requiredNo ICLNo light (LED is off)ATTN LED
Ensure ICL cable is correctly
installed.
Attention requiredBlinking amber
Monitoring power supply status
To determine power supply status:
1. Observe the LED indicator on the power supply (see Figure 31 (page 62)). The LED patterns
may temporarily change during POST and other diagnostic tests; for information about how
to interpret the LED patterns, see Table 12 (page 62).
2. Enter the psShow command to verify power supply status.
The power supply status displays OK, Absent, or Faulty. If a power supply is absent or faulty,
contact HP to order replacement power supply.
Monitoring power supply status 61