HP DC04 SAN Director Switch Hardware Reference Guide
Table 7 Torque requirements
TorqueScrew size
10 cm-kg (8.75 in-lb)6-32 x .635 cm (0.25 in) Phillips screw
36.86 cm-kg (32 in-lb)10-32 x 1.60 cm (0.63 in) Phillips screw
Installing the cabinet hardware
1. Position the DC04 SAN Director in the equipment cabinet so that the non-port side has access
to cool intake air.
2. Install the mounting nuts in the cabinet rail locations shown in Figure 5 (page 23). These nuts
secure the 10-32 screws that mount the port-side exhaust kit shelf and DC04 SAN Director to
the cabinet.
• For rails with round holes—Install the clip nuts (F in Figure 4 (page 22)).
• For rails with square holes—Install the retainer nuts (G in Figure 4 (page 22)).
The location shown in Figure 5 (page 23) is an example. The shelf and DC04 SAN Director
can be installed anywhere in the cabinet that has 9U of space available.
Figure 5 Clip and retainer nut locations on cabinet rails
Installing the DC04 SAN Director in a rack 23