HP DC SAN Backbone Director Switch Hardware Reference Guide

System blade and FRU weights
Table 23 System FRU weights
WeightFRU
3.0 kg (6.6 lb)CP blade (CP8)
3.27 kg (7.2 lb)CR blade (CR8, CR4S-8)
3.0 kg (6.6 lb) without mediaFC8-16 port blade
3.27 kg (7.2 lb) without mediaFC8-32 port blade
3.36 kg (7.4 lb) without mediaFC8-48 port blade
3.36 kg (7.4 lb) without mediaFC8-64 port blade
3.1 kg (6.8 lb) without mediaFC10-6 port blade
3.36 kg (7.4 lb) without mediaFR4-18i application blade
5.5 kg (12.0 lb)FS8-18 encryption blade
4.2 kg (9.2 lb) without mediaFX8-24 Multi Protocol Extension blade
4.2 kg (9.2 lb) without mediaFX8-24E Enhanced Multi Protocol Extension blade
3.72 kg (8.2 lb) without mediaFCOE10-24 FCoE blade
1.5 kg (3.2 lb)Port card filler panel
2.45 kg (5.4 lb)Power supply
5.73 kg (12.6 lb)Blower assembly
0.3 kg (0.6 lb)WWN bezel
0.45 kg (1.0 lb)Cable management comb
0.3 kg (0.6 lb)WWN bezel
2.09 kg (4.6 lb)Chassis door
Facility requirements
The facility where the product is in use must meet the following requirements to provide for correct
operation:
Adequate supply circuit, line fusing, and wire size, as specified by the electrical rating on the
chassis nameplate
An air flow of at least 595 cubic meters per hour (350 cubic feet per minute) in the immediate
vicinity of the DC SAN Director
The power specifications listed in Table 24 (page 105)
The environmental specifications listed in Table 27 (page 109)
If the product will be installed in an EIA rack, ensure the following:
All equipment installed in the rack has a reliable branch circuit ground connection and
does not rely on a connection to a branch circuit, such as a power strip.
The rack is balanced and mechanically secured to provide stability in the event of an
earthquake.
Additional equipment does not exceed the weight limits of the rack.
104 Technical specifications