HP StoreOnce 6500 Backup Installation Planning and Preparation Guide
Location
At the time of placing the order, make sure that there is a suitable location with access to install
the product. This must be a data center environment and not an office environment. (See Product
specifications (page 16) for more details.) It should conform to the following requirements:
The receiving dock, storage area, and receiving area are large enough to allow movement of
and access to crated or packed equipment.
1.
The floors, elevators, and ramps are able to support the weight of the delivered equipment as it
is moved to the installation location.
2.
The installation location must provide:3.
• Sufficient space to accommodate the installed product.
nl
When installing two racks, the units should be located next to each other to ensure there are
no problems with cable lengths.
NOTE: Sufficient space, at least 12 inches (30 cm), must be available to the right-hand side
of the rack to ensure that there is enough clearance to maneuver the disks in and out of drawer
2.
• Appropriate power, air conditioning, cabling, and fire protection.
• Adequate protection from electrostatic discharge (ESD).
• Adequate protection from electrical/radio frequency interference.
• Adequate protection from dust, pollution, and particulate contamination
• Adequate acoustic insulation for operating the system.
Power/PDU requirements
At the time of placing the order, make sure that the location can support the HP StoreOnce Backup
System’s input power and power outlet requirements. The AC power input for the HP StoreOnce
Backup System has a duplex PDU structure, this means that between two and four PDUs must be
connected, depending on configuration.
Prior to installation you should confirm that you have specified the correct PDU for your geographical
location and connector type and that you have sufficient power outlets. See Power/PDU
requirements (page 16).
NOTE: The Power/PDU requirement varies depending upon the number of racks, couplets and
storage, and the input voltage.
PDU option and connector type
Please provide details of:
1.
PDU option: ..................................................................................................................
Connector plug type:.............................................................................................................
Connector socket type:.............................................................................................................
Power outlets, two outlets are required for the each couplet. But it is strongly recommended that
each rack be installed with four outlets to allow for ease of expansion, even if the rack has only
one couplet.
2.
Please record:
Number of power outlets available:...................................................................................
6 Checklists for completion prior to installation