HP StoreOnce 6500 Backup Installation Planning and Preparation Guide
PDU options
Two different types of PDU are available. HP’s standard “Modular” PDUs and HP’s “Intelligent
Modular” PDUs.
For further information on PDU features, refer to http://www.hp.com.
Each HP StoreOnce 6500 rack is supplied with four PDUs that are connected to four pairs of
extension bars.
IMPORTANT: You must specify which power option will be used when placing the order for the
HP StoreOnce Backup system.
Table 9 Standard Modular PDU options
InternationalNorth America and Japan
16A 3Ø wye
380–415V
32A 1Ø 200-240V41.52A 3Ø delta
208V
24A 1Ø 200-240VOutput
3.6m attached cable,
IEC 60309 4 pole, 5
3.6m attached cable,
IEC309-32A
3.6m attached cable,
NEMA L15-30P
3.6m attached cable,
L6-30P
Connector plug type
wire, 380-415VAC,Splashproof (IEC
332P6S) 16A, Splashproof (IEC
516P6S)
IEC60309 4 pole, 5
wire, 380-415 VAC,
IEC60309 2 pole, 3
wire, 200- 240VAC,
208V 3 phase 3 pole
4 wire (Delta) NEMA
L15-30R
NEMA L6-30RFacility Power
Connection
16A IEC 516C6S,
516R6S, or equivalent
32A IEC 332C6S,
332R6S, or equivalent
4444Number of PDUs per
rack
4444Number of sockets
required per rack
AF513A252663-B33AF512A252663-D74Part number
Table 10 Extension Bars for Standard Modular PDUs
HP Two C13 PDU Extension Bars
nl
(All Regions)
Each extension bar has a C-19 input and 7 C-13
receptacles
Input/Output Connections
Four pairsNumber per rack
AF500APart Number
Table 11 Intelligent Modular PDU options
InternationalNorth America and Japan
16A 3Ø wye
380–415V
32A 1Ø 200-240V41.52A 3Ø delta
208V
24A 1Ø 200-208VOutput
3.6m attached cable,
IEC 60309 4 pole, 5
3.6m attached cable,
IEC309-32A
3.6m attached cable,
NEMA L15-30P
3.6m attached cable,
L6-30P
Connector plug type
wire, 380-415VAC,Splashproof (IEC
332P6S) 16A, Splashproof (IEC
516P6S)
Power/PDU requirements 17