UserÆs Guide and Technical UserÆs Guide - HP Carrier Grade Server cc3300

HP cc3300 Carrier Grade Server Product Guide
Chassis Description 15
Kcal per hour 45 Cal/sec
Nominal rated voltages 100 – 240 V
Maximum operating voltage 264 V
Minimum operating voltage 87 V
Rated (marked) line current(s) 4 / 2 Amps
Line voltage power-fail threshold 73 V
Dropout carry-through time at minimum line voltage 20 mSec
Mating AC input receptacle type C-13 C13, etc
Branch circuit breaker size at 100 VAC 15/20 Amps
Branch circuit breaker size at 120 VAC 15/20 Amps
Frequency range non-strappable 47 - 66 Hz
DC input (if applicable) 48 Volts nominal
DC input (if applicable) 4.6 Amps
EMC
Radiated filed immunity – what frequencies are sensitive below 10 v/m None
ESD immunity – Maximum kV with no loss of function 4/8 kV
ESD immunity – Maximum kV with no component damage 4/8 kV
Sound power level (LWA) 6.8 B
Sound pressure level (LPA) at operator position 50.3 dB
Transient spike immunity amplitude 2 Kv
Transient spike immunity duration 50 Micro Sec.
Transient spike immunity rise time 1.2 Micro Sec.