WARNING
Do not attempt to modify or use an AC power cord that is not the exact
type required. You must use a power cord that meets the following
criteria:
1. Rating: For U.S./Canada cords must be UL Listed/CSA Certified
type SJT, 18-3 AWG. For outside U.S./Canada cords must be
flexible harmonized (<HAR>) or VDE certified cord with
3 x 0.75mm conductors rated 250 VAC.
2. Connector, wall outlet end: Cords must be terminated in
grounding-type male plug designed for use in your region. The
connector must have certification marks showing certification by an
agency acceptable in your region and for U.S. must be rated
125% of overall current rating of the server.
3. Connector, server end: The connectors that plug into the
AC receptacle on the server must be an IEC 320, sheet C13, type
female connector.
4. Cord length and flexibility: Cords must be less than 4.5 meters
(14.76 feet) long.
CAUTION
Temperature: The temperature, in which the server operates when installed
in an equipment rack, must be maintained between 5 °C (41 °F) and 40 °C
(104 °F). Extreme fluctuations in temperature can cause a variety of
problems in your server.
Ventilation: The equipment rack must provide sufficient airflow to the front
of the server to maintain proper cooling. The rack must also include
ventilation sufficient to exhaust a maximum of 1023 BTU's per hour for each
installed server. The rack selected and the ventilation provided must be
suitable to the environment in which the server will be used.