Fabric OS Message Reference v7.0.0 (53-1002149-01, April 2011)

414 Fabric OS Message Reference
53-1002149-01
HIL-1502
48
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well-ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
Severity WARNING
HIL-1502
Message <timestamp>, [HIL-1502], <sequence-number>, FFDC, CRITICAL, <system-name>, Slot
<slot number>, high temperature (<measured temperature>). Unit will be shut down
in 2 minutes if temperature remains high.
Probable Cause Indicates that the temperature of this blade has risen above the critical threshold. This usually
follows a high-temperature message.
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well-ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
If the message persists, replace the blade.
Severity CRITICAL
HIL-1503
Message <timestamp>, [HIL-1503], <sequence-number>, FFDC, CRITICAL, <system-name>, Slot
<slot number>, unit shutting down.
Probable Cause Indicates that the temperature of this blade has been above the maximum threshold for at least
two minutes. The blade is shut down to prevent damage. This usually follows a high-temperature
warning message.
Recommended
Action
Run the fanShow command to verify all the fans are working properly.
Make sure that the area is well-ventilated and that the room temperature is within operational
range of your switch. Refer to the hardware reference manual for your switch for the operational
temperature range.
If the message persists, replace the faulty blade.
Severity CRITICAL
HIL-1504
Message <timestamp>, [HIL-1504], <sequence-number>,, INFO, <system-name>, System within
normal temperature specifications (<measured temperature> C).
Probable Cause Indicates that temperatures in the system have returned to normal.