HP Apollo a6000 Chassis Maintenance and Service Guide

Specifications 48
Three-phase power (North America/Japan)
Specification
HP 2450W Platinum Hot Plug
Redundant Power Supply
HP 2650W Platinum Hot Plug
Redundant Power Supply
Power cord
NEMA L15-30p
3.05 m (10 ft)
NEMA L15-30p
3.05 m (10 ft)
Output
2450 W per phase 2650 W per phase
Input requirements
Rated input voltage
200 VAC to 208 VAC line to line
3-phase delta
200 VAC to 208 VAC line to line
3-phase delta
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz
Maximum input current per
line cord
22.9 A at 200 VAC
22 A at 208 VAC
25 A at 200 VAC
24 A at 208 VAC
Maximum input power per
line cord
7920 VA 8640 VA
Three-phase power (International)
Specification
HP 2450W Platinum Hot Plug
Redundant Power Supply
HP 2650W Platinum Hot Plug
Redundant Power Supply
Power cords (2)
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
IEC-309 200/380-V to 240/415-V,
5-pin, 16-A
3.05 m (10 ft)
Output
2450 W 2650 W
Input requirements
Rated input voltage
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
380 VAC to 415 VAC line-to-line*
220 VAC to 240 VAC line-to-neutral
3-phase WYE
Rated input frequency
50 Hz to 60 Hz 50 Hz to 60 Hz
Maximum input current per
line cord
12.2 A at 220/380 VAC
11.2 A at 240/415 VAC
13.1 A at 220/380 VAC
12 A at 240/415 VAC
Maximum input power per
line cord
8064 VA 8646 VA
*Rated 220 VAC to 240 VAC line-to-neutral. The enclosure does not operate from higher line-to-line voltage with the
WYE wall plug configuration. Input AC modules are configured to provide 220 VAC to 240 VAC to the power supplies
in this system.