HP V142 Rack Options Installation Guide

Ground Bonding kit 9
Ground Bonding kit
About this device
The HP V142 Rack Ground Bonding kit reduces the electromagnetic emissions outside the rack. These
emissions are produced during normal operation of the electronic components within the rack. Typically,
rack-mounted equipment must meet class A emissions levels, but you can reduce these levels even further.
Use this kit to tie all the conductive structural components together with conductive cables, and then attach
the kit to a ground bonding point on the AC power distribution device of the rack or the building ground.
Kit contents
Item Quantity
15.24-cm (6-in) grounding straps 10
M6 ground washer 14
M6 ground nut 14
This kit might contain extra hardware for your convenience.
Required tools
T-25 Torx driver
M6-socket
Installing the Ground Bonding rack option kit on HP
V142 Racks
Attach the grounding straps to the following locations:
From the front rack frame to the front door
1. Place one end of the grounding strap over the grounding lug on the front rack frame.