HP V142 Rack Options Installation Guide
Ground Bonding kit 12
Reference Item
3 M6 ground washer
4 Facility ground (not included with this kit)
5 M8 x 20 bolt
From the rack frame to the top side panel, if installed:
1. Place one end of the grounding strap over the grounding lug on the rack frame.
2. Place an M6 ground washer and an M6 ground nut over the grounding lug on the rack frame, and
then tighten the ground nut.
3. Place the other end of the same grounding strap over the grounding lug on the top side panel.
4. Place an M6 ground washer and an M6 ground nut over the grounding lug on the top side panel,
and then tighten the ground nut.
5. Repeat steps 1 through 4 for the other top side panel.
From the rack frame to the bottom side panel, if installed:
1. Place one end of the grounding strap over the grounding lug on the rack frame.