User Service Guide, Fifth Edition - HP 9000 rp4410/4440

C Physical and Environmental Specifications
Table C-1 provides temperature and airflow information for minimum, typical, and maximum
configurations for the HP 9000 rp4410 and rp4440 servers. It also lists the server and rack weights
and dimensions.
Table C-1 Physical and Environmental Specifications
Overall Server
(W x D x H)
WeightCondition
Airflow, at
Maximum
Ambient degrees
C
1
Airflow, NominalTypical
Heat
Release
Pede-stalRackPede-stalRackServer
Alone
180-264
VAC
W: 10.3 in
(26.1 cm)
D: 27.4 in
(69.5 cm)
H: 20.9 in
(53.0 cm)
W: 19 in
(48.2 cm)
D: 27.2 in
(69.0 cm)
H: 6.8 in
(17.3 cm)
115 lbs
(53 kg)
100 lbs
(45.4 kg)
88 lbs
(40 kg)
425
m3/hr
250
CFM
297
m3/hr
175 CFM
410 WattsMin.
Config.
1368 WattsMax.
Config.
1065 WattsTypical
Config.
One CPU, one power supply, 1 GB DIMM, zero DVD,
one HDD, zero PCI cards, one core I/O.
Min./
Config.
Airflow cooling scheme (front to rear)ASHRAE
Class 1
Four CPUs, two power supplies, 128 GB DIMM, one
DVD, two HDD, six PCI cards, two core I/O.
Max.
Config.
Two CPUs, two power supplies, 16 GM DIMM, one
DVD, two HDD, two PCI cards, one core I/O.
Typical
Config.
1 Derate maximum dry bulb temperature 1 degree per 300 meters above 900 meters.