HP StorageWorks 4x00/6x00/8x00 Enterprise Virtual Array hardware configuration guide (5697-7338, February 2008)
B L ow-voltage Japanese ca binets
General description
This specification describes HP's requirements for low voltage EVA storage cabinets. These low voltage
cabinets are configured with two redundant sets of PDUs in order to provide system required power. Each
PDU set is limited to 2550 W at a minimum voltage of 108. Each PDU is limited to one power strip
to limit the number of EVA component attachment to eight components per power PDU. Power strip
additions will likely overload the PDU systems.
Reference documents
Reference documents are for informational purposes only. No requirement is implied by the inclusion
or exclusio
n of reference documents.
• ANSI/EIA-310-D-1992, Cabinets, Racks, Panels a nd Associated Equipment
• EN60950:2000, Safety of Information Technology Equipment
• FCC Part 15
Code of Federal Regulations, Title 47, FCC Part 15 Radio Frequency Devices,
Subpart B, Unintentional Radiators
• EN55022 (1 998) , Limits and Metho ds of Measurement of Radio Interference Characteristics of
Informati
on Technology Equipment
• EN55024 (1998), Information Technology Equipment – Immunit y Characteristics and M ethods
of Measu rement
• EN61000, Electromagnetic Compatibility
• CAN/CSA
-C22.2 No. 60950-00/3rd Edition, Safety of Information Technology Equipment
All bran
ds, names, trademarks and logos are the property of their respective owners.
Power configurations
There are two power configurations: the AD572A and the AD573A. The AD572A uses the HP
StorageWorks 42 U Low-voltage cabinet (Figure 35) and the AD573A uses the HP StorageWorks 36U
Low-voltage cabinet (Figure 36).
4x00/6x00/8x00 Enterprise Virtual Array hardware configuration guide
59