HP StorageWorks 4x00/6x00/8x00 Enterprise Virtual Array hardware configuration guide (5697-7338, February 2008)
Table 21 EVA6x00 power specifica tions — 208 Vo lts
Specification
2C4D 2C5D 2C6D 2C7D 2C8D
Total System
Wattage
1837
2214
2590 296 7
3344
Total System
BTU/hour
6 2 68 7 5 5 3 8838
10124 11409
Input Current
(A) - Typical
per system
4.6
5.5
6.5 7.4 8.4
Typical
1
In Rush Current
(A)
220 250 280 321 363
Failover Mode
Input Current
(A) - Maximum
per system
7. 8
9.4
11.0 12.6
14.2
1
Typical is described as a system in normal steady state operation (that is, both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive t ypes may vary slightly. For example, if
you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K RPM drives.
Table 22 EVA6x00 power specifications — 230 Volts
Specificati
on
2C4D 2C5D 2C6D 2C7D 2C8D
Total System
Wattage
1837 2214 2590 296 7 3344
Total System
BTU/hour
6 2 68 7 5 5 3 8838
10124 11409
Input Current
(A) - Typical
per system
4.3
5.2 6.1 7.0 7.9
Typical
1
In Rush Current
(A)
244
272 311 357
403
Failover Mode
Input Current
(A) - Maximum
per system
7.3 8.8 10.0 11.9 13.3
1
Typical is described as a system in normal steady state operation (that is, both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive t ypes may vary slightly. For example, if
you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K RPM drives.
56
Specifications