Table 18 Power Da ta (Nort h America/Europe/Japan) ma ximum c onfigura tion
AC plug type (qu
antity 2)
North America –
3wireNEMANo. L6-30P,30amp(208to240V,50–60Hz,
30A)
Europe – 3 wire,
2poleIEC309,30amp,(220to240V,50Hz,32A)
Number of phases
Single
Rated current 17A @ 200V-240V AC, 60Hz total, 4.25 A per power cord
Nominal Line V
oltage
North America
–208or230V
Europe – 230V
Japan – 206V
RangeLineVoltage
187 to 256V
Line Frequency
NorthAmerica60Hz,Europe50Hz,Japan50or60Hz
Table 19 EVA4x00 power specifications — 208 Volts
Specification
2C1D 2C2D 2C3D 2C4D
Total System
Wattage
638 1013 1390 1767
Total Syste
m
BTU/hour
17 29 3014 4300 5 585
Input Current (A) -
Typical per system
1.6 2.6 3.5
4.4
Typical
1
In Rush Current (A)
98 132 17 0 220
Failover Mode
Input Current (A)
- Maximum per
system
2.7
4.3
5.9
7.5
1
Typical is described as a system in normal steady state operation (that is, both PDUs operating normally, the array
reading/writing to disk drives in a production environment).
This data represents fully populated drive enclosures with 15K RPM disk drives. Other drive types m ay vary slightly. For example, if
you are using 10K RPM drives, the power specifications will be approximately 20% less than the 15K RPM drives.
Table 20 EVA4x00 power specifications — 230 Volts
Specification
2C1D 2 C2D 2C3D 2C 4D
Total System
Wattage
638 1013 1390 1767
Total System
BTU/hour
1729
3014 4300
5585
Input Current (A) -
Typical per system
1.5
2.4
3.3
4.2
Typical
1
In Rush Current (A)
104 147
190
244
Failover Mode
Input C
urrent (A)
-Maxim
um per
system
2.6
4.1
5.5 7.1
1
Typi
cal is described as a system in normal steady state operation (that is, both PDUs operating normally, the array
readi
ng/writing to disk drives in a production environment).
This da
ta represents fully populated drive enclosures with 15K RPM disk drives. Other drive types may vary slightly. For example, if
you are
using 10K RPM drives, the power specifications will be approximately 20% less than the 15K RPM drives.
4x00/6x00/8x00 Enterprise Virtual Array hardware configuration guide