HP StorageWorks 4x00/6x00/8x00 Enterprise Virtual Array hardware configuration guide (5697-7338, February 2008)
Table 16 Environmental specification s
Operating Temperature
50° to 95° F (10° to 35° C) - Reduce rating by 1° F for each 1000 ft altitude
(1.8° C/1,000 m
)
Shipping Temp erature
-40° to 150° F (-40° to 66° C)
Humidity 10% to 90% non-cond en sing
Shipping Humidity 5% to 90% non-condensing
Altitude
Up to 8,000 ft (2,400 m)
Air Quality
Not to exceed 500,000 particles per cubic foot of air at a size of 0.5 micron
or larger
Power specifications
The input voltage is a function of the country-specific input voltage to Enterprise storage system rack
power distribution units (PDUs). Enterprise storage system A C input line voltages defines the AC input
power available to the drive enclosure power supplies.
CAUTION:
The AC power
distribution within a rack ensures a balanced to each PDA and reduces the possibility of
an overload condition. Changing the cabling to or from a PDM could cause an overload condition.
Table 17 Enterprise storage system AC input line voltages
Specification
Minimal Nominal
Maximum
60 Hz service
AC Line Voltage
57 Hz
60 Hz 63 Hz
AC Line Voltage—Japan
180 VAC 202 VAC 220 VAC
AC Line Voltage–North America
180 VAC 208 VAC 220 VAC
AC Line Voltage–Europe
208VAC 240VAC 254VAC
50 Hz service
AC Line Frequency 47 Hz
50 Hz 53 Hz
AC Line Voltage–Japa n
180 VAC 202 VAC 220 VAC
AC Line Voltage–North America
190VAC 220VAC 235VAC
AC Line Voltage–North America
200 VAC 230 VAC 244 VAC
AC Line Voltage–Europe
208VAC 240VAC 254VAC
54
Specifications