HP 3PAR StoreServ 7450 Storage Troubleshooting Guide
cli% showbattery
Node PS Bat Serial -State-- ChrgLvl(%) -ExpDate-- Expired Testing
3 0 0 100A300B OK 100 07/01/2011 No No
3 1 0 12345310 Failed 0 04/07/2011 No No
Node Example 3
Component -Identifier- --------------Description----------------
Node node:3 Node:3, Power Supply:1, Battery:0 has not been tested within
the last 30 days
Node Suggested Action 3
The indicated battery has not been tested in the past 30 days. A node backup battery is tested
every 14 days under normal conditions, but if a battery is missing, expired, or failed, it is not
tested. In addition, the other battery connected to the same node is not tested because testing it
would cause loss of battery backup to the node, and the system does not allow that. An untested
battery has an Unknown status in the showbattery -s output. Use commands such as
showbattery, showbattery -s, and showbattery -d.
showbattery -s
Node PS Bat -State-- -Detailed_State-
0 0 0 OK normal
0 1 0 Degraded Unknown
Examine the date of the last successful test of that battery. Assuming the comment date was
2009-10-14, the last battery test on Node 0, PS 1, Bat 0 was 2009-09-10, which is more
than 30 days ago.
showbattery -log
Node PS Bat Test Result Dur(mins) ---------Time----------
0 0 0 0 Passed 1 2009-10-14 14:34:50 PDT
0 0 0 1 Passed 1 2009-10-28 14:36:57 PDT
0 1 0 0 Passed 1 2009-08-27 06:17:44 PDT
0 1 0 1 Passed 1 2009-09-10 06:19:34 PDT
showbattery
Node PS Bat Serial -State-- ChrgLvl(%) -ExpDate-- Expired Testing
0 0 0 83205243 OK 100 04/07/2011 No No
0 1 0 83202356 Degraded 100 04/07/2011 No No
PD
Displays Physical Disks (PDs) with states or conditions that are not optimal:
• Checks for failed and degraded PDs
• Checks for an imbalance of PD ports, for example, if Port-A is used on more disks than Port-B
• Checks for an Unknown Sparing Algorithm. For example, when it hasn't been set
• Checks for disks experiencing a high number of IOPS
• Reports if a servicemag operation is outstanding (servicemag status)
• Reports if there are PDs that do not have entries in the firmware DB file