3PAR InForm® OS 2.3.1 Messages and Operator's Guide (320-200181 Rev B, February 2010)

InForm OS Version 2.3.1 Messages and Operator’s Guide
10.1
Power Off/On Procedures
10
Power Off/On Procedures
In this chapter
10.1 Powering Off the Storage Server 10.1
10.2 Powering On the Storage Server 10.4
10.1 Powering Off the Storage Server
The following procedure describes how to safely remove power from the InServ Storage Server
and Service Processor.
1 SSH to the Service Processor or physically connect a maintenance PC to the serial
connection.
2 Log in to the service processor by entering your login name and password.
3 If necessary, enter spmaint to get to the spmaint main menu.
4 Select option 4, InServ Product Maintenance.
NOTE: PDUs in any expansion cabinets connected to the InServ Storage Server
may need to be shut off. Use the locatesys command to identify all connected
cabinets.
locatesys will blink all node and drive cage LEDs. Note this
information now, as it is needed for step 12 on page 10.4.