3PAR InServĀ® E-Class/F-Class Storage Server Physical Planning Manual (320 - 200120 Rev F, September 2010)

5.9
3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual
Watts 730
BTUs/hour (fully populated) 2491 BTUs/hr
Input Voltage 100-240 VAC
Frequency 50-60 Hz
Power Receptacle (2) IEC-320 for 1+1 redundancy.
F400 Controller Node Chassis (Quad Node)
Watts 1460
BTUs/hour (fully populated) 4,982 BTUs/hr.
Input Voltage 100-240 VAC
Frequency 50-60 Hz
Power Receptacle (2) IEC-320 for 1+1 redundancy.
Drive Chassis
Watts 525
BTUs/hour (fully populated) 1,792 BTUs/hr.
Input Voltage 100-240 VAC
Frequency 48 - 62 Hz
Power Receptacle (2) IEC-320 with 1+1 rdnt.
Service Processor
Supermicro
Watts
260
Table 5-1. Power and Heat Specifications (continued)