3PAR InServĀ® E-Class/F-Class Storage Server Physical Planning Manual (320 - 200120 Rev F, September 2010)

2.10
3PAR InServ E-Class/F-Class Storage Server Physical Planning Manual
2.5 Power and Heat Specifications
Table 2-3 describes electrical current requirements and heat dissipation for the E-Class/F-Class
Storage Servers.
Table 2-3. Power and Heat Specifications
1 Meter Cabinet (Only available for the E200)
Max. Watts per Cabinet (fully
populated)
2,880
Max. BTUs/hour per cabinet
(fully populated)
9,825
Input Voltage (VAC) (200 - 240)
Frequency (Hz) (50 - 60), 1-phase 50/60
Circuit Breaker Max 30 amps per PDU (de-rated to
24 amps)
Power Connectors (provided) (2) L6-30P for 1+1 redundancy