HP StoreEver 1/8 G2 Tape Autoloader User and Service Guide (AK377-96024, December 2012)
Table 34 Warning event codes (continued)
Details and SolutionDescriptionEvent code
The autoloader will only accept signed firmware
images. Download a signed firmware image.
Invalid firmware version. Only signed firmware
images are allowed.
7B
Recovered error move operation. No action
required. Occasional retries are normal operation.
Movement retry. Robotics movement did not
succeed but was successful on a retry.
80
• Check the tape drive fan on the autoloader
back panel to see whether the fan is
operational and not obstructed.
NOTE: Fan only operates when cooling is
required.
Drive sled fan alert. Fan motion has stopped.81
Clean the tape drive using a valid cleaning tape.Clean request from the tape drive82
Evaluate media status using L&TT.Media attention83
Evaluate drive status using L&TT.Tape drive tape alert; tape drive reported a
warning or critical tape alert.
84
DHCP request has failed85
• Check the network to ensure connection to the
DHCP server.
• Check that the network configuration is correct.
• If DHCP is enabled, ensure that the DHCP
server is up and running on the device's
network.
• Power cycle the device and retry the operation.
Insert a valid cleaning cartridge into the
autoloader.
Autoclean media warning; not enough media
present to support autocleaning.
86
Replace the drive with a compatible tape drive.Drive not supported; the tape drive was disabled
because it cannot be used in this autoloader.
87
Drive firmware revision has not changed after a
tape drive firmware upgrade.
88
• Verify that the firmware image is correct for the
tape drive.
• Retry the operation.
• Retry using an alternate firmware upgrade
method.
Install new autoloader firmware, which will install
a compatible robotics firmware version.
Invalid robotics code; does not match with the
loaded autoloader firmware.
8C
Obtain a new cleaning tape for use when the
current cleaning tape expires.
Cleaning tape nearly expired. Only one or two
cleaning operations remain.
8E
Contact HP Service if this unexpected condition
occurs.
I
2
C bus recovery8F
Power cycle the device and retry the operation.VPD data recovery.92
Verify that the fan for the indicated drive sled is
operational and not obstructed.
External drive cooling fan failure (fan motion has
stopped). The subcode indicates which drive sled
fan is affected.
DB
NOTE: The fan only operates when cooling is
required.
Subcode 00: drive sled #1
Subcode 01: drive sled #2
etc.
124 Troubleshooting