Installation manual

FuelMaster
®
Installation Manual
94
count cannot exceed 9000 pulses per minute. The pulse count is determined by multiplying the
flow rate (i.e., 9 gallons per minute) times the divide rate (i.e., 100 pulses per gallon). This
example would be 900 pulses per minute. Separating the AC control wires and DC pulser cables
in separate conduit will also eliminate any bleedover.
e. One Pulser, Two FMUs.
CAUTION
Power inputs (+12V) from two different FMUs or power sources to a single pulser can result in
damage to both FMUs and, possibly, the pulser. If possible, power the pulser from only one
power source. DC grounds (0V) from both sources must be joined (made common) for pulses to
be detected by both FMUs. Grounds must not
be joined (made common) unless both power
sources are 12 VDC. AC grounds are not the same as DC commons/grounds.
ATTENTION
Des entrées d'alimentation (+12 V) de deux FMU différentes sources ou de la puissance d'un
émetteur unique peut entraîner des dommages aux deux FMU et, éventuellement, le générateur
d'impulsions. Si possible, le pouvoir du pulseur d'une seule source d'alimentation. motifs DC
(0V) à partir de deux sources doivent être rejoint (en commun) pour les légumineuses à détecter
par les deux FMU. Motifs ne doit pas être rejoint (en commun) à moins que les sources
d'énergie sont de 12 VDC. AC motifs ne sont pas les mêmes que Commons CC / motifs.
Applications have been requested for one pulser in one dispenser to provide outputs to two
FMUs. When doing so, caution must be used in making pulser connections. Power inputs (+12V)
from two different FMUs or power sources to a single pulser may result in damage to the FMUs
and pulser. Power from either source will feed back to the other source and may result in
damage to both FMUs and, possibly, the pulser. DC commons/grounds (0V) from both sources
must be joined (common) for pulses to be detected by both FMUs. Grounds must not be joined
(made common) unless both power sources are 12 VDC. If the power sources are not both 12
VDC, and the grounds are not joined (common), pulses from a single pulser to two FMUs will not
be detected. AC grounds are not the same as DC commons/grounds.
270