Installation manual

2) If a solenoid valve is not installed, verify fuel stops flowing when the transaction is ended
by squeezing the nozzle trigger after the pump handle switch is turned off. Fuel should
not flow.
l. PROTECT DATA DURING POWER FAILURE. Repeat for multiple FMUs. Note any
deviations on page 5.
1) In automatic mode, when power was removed from each FMU the applicable dispensers
connected to that FMU were disabled.
2) Transactions in progress during power failure were recorded. No transaction data was
lost.
3) When power was restored to each FMU the applicable dispensers connected to that FMU
did not activate without initiating a new transaction.
4) Manual intervention was not required to bring the system to full operation after power
failure.
m. PRICING. Repeat for multiple FMUs. Note any deviations on page 5.
1) Check all price levels stored at the FMU
2) If receipts for ProKee is turned on verify that the price on the receipt is correct
3) If credit card, run a few transactions verify pricing and functionality
n. DISCOUNT CREDIT CARDS. Repeat for multiple FMUs. Note any deviations on page 5.
1) Set up discount credit card in software and send to FMU
2) Run a test transaction and verify that proper price level appear
o. PREPAID CARDS/KEYS. Repeat for multiple FMUs. Note any deviations on page 5.
1) Set up a pre-paid record in the software, encode and send it to the FMU
2) Run a test transaction and verify functionality
3) Download transactions and make sure that card record reflects transaction
p. RECORD TRANSACTION DATA. Perform automated test transactions on each hose.
Record the quantity displayed on the dispenser as DISPENSER QTY. Go to the Central
Controller and download the test transactions and record them under POLLED QTY.
HOSE DISPENSER POLLED HOSE DISPENSER POLLED
# QTY QTY # QTY QTY
1 9
2 10
3 11
4 12
5 13
6 14
7 15
8 16
Page 3 of 5