m. PRICING. Repeat for multiple FMUs. Note any deviations on page 6.
1) Check all price levels stored at the FMU
2) If receipts for ProKee is turned on verify that the price on the receipt is correct
3) If credit card, run a few transactions verify pricing and functionality
n. DISCOUNT CREDIT CARDS. Repeat for multiple FMUs. Note any deviations on page 6.
1) Set up discount credit card in software and send to FMU
2) Run a test transaction and verify that proper price level appear
o. PREPAID CARDS/KEYS. Repeat for multiple FMUs. Note any deviations on page 6.
1) Set up a pre-paid record in the software, encode and send it to the FMU
2) Run a test transaction and verify functionality
3) Download transactions and make sure that card record reflects transaction
p. RECORD TRANSACTION DATA. Perform automated test transactions on each hose.
Record the quantity displayed on the dispenser as DISPENSER QTY. Go to the Central
Controller and download the test transactions and record them under POLLED QTY.
HOSE DISPENSER POLLED HOSE DISPENSER POLLED
# QTY QTY # QTY QTY
1 9
2 10
3 11
4 12
5 13
6 14
7 15
8 16
q. DELAY COUNTS. In step 1d, a test was performed to determine if the dispensing equipment
registered quantity before any fuel was delivered. If the answer was NO, omit this step. If the
answer was YES, counts (pulses) must be delayed until the dispensing hoses are fully
pressurized, and
the counter must be capable of being reset to 0 (zero), or replaced with a
counter that starts counting after the hose is pressurized. The visible counter and pulse
delivery must both be delayed.
1) Is the dispenser capable of being programmed to delay visible counts and pulse delivery?
YES / NO (circle one) If YES, determine how much delay (in seconds) is needed, and
program the delay into the dispensing equipment. Delay Length:
2) If the answer to q1, above, is NO because visible counts are displayed, can the
dispensing equipment counter be reset to 0 (zero) after the hose is pressurized?
YES / NO (circle one) If NO, a substitute counter must be installed that starts counting
after the hose is fully pressurized. Substitute counter:
If YES, self serve procedures must inform customer to reset counter to 0 (zero) after the
hose pressurizes.