Installation manual

FuelMaster
®
Installation Manual
146
Large Remote Display:
An optional Large Remote Display provides a quantity display with four inch LED digits visible up to 150
feet. The Large Remote Display is wired into the pulser circuit which provides quantity information to the
FMU. The display is preprogrammed at the factory to match the pulser divide rate. As such, the quantity
shown on the display is identical to the quantity recorded by the FMU.
Detailed installation procedures for the Large Remote Display may be found in Product Bulletin 125. If
two fueling points such as AVGAS and Jet A are close together, and not subject to simultaneous
operation, one Large Remote Display may be installed in accordance with the Product Bulletin to support
both fueling points.
The Large Remote Display is not explosion-proof and must be installed outside and above the hazardous
area. It is provided with two removable mount brackets attached to the center top and bottom. There is no
access hole drilled into the aluminum housing for incoming conduit/wires. The installer selects the most
ideal location, and drills/punches a hole for the connecting conduit. The Large Remote Display is
available in the same colors as the FMU.
A Reset Oink is mounted inside the Large Remote Display. The Reset Oink uses a 110 VAC input from
the authorization signal to reset the display each time a new transaction is started. The Large Remote
Display requires AC power to run it, and a 12 VDC pulse input to increment the digits on the display as
fuel is pumped.
Large Remote Display on FMU