Installation manual

FuelMaster
®
Installation Manual
109
3. To change the satellite configuration to an EIU, depress the space bar until GATE MASTER is
displayed, then depress ENTER:
USAGE - <SPACE>=CHANGE VALUE, <ENTER>=NEXT FIELD, <ESC>=EXIT
----------------------------------------------------------------------------------------------------------
EIU SETUP FOR SAT#1:
GATE MASTER
USING PROKEES!
4. If USING PROKEES! is not desired, depress the space bar to change to NOT USING
PROKEES!:
USAGE - <SPACE>=CHANGE VALUE, <ENTER>=NEXT FIELD, <ESC>=EXIT
----------------------------------------------------------------------------------------------------------
EIU SETUP FOR SAT#1:
GATE MASTER
NOT USING PROKEES!
NOTE
If an invalid EIU configuration is selected, the prompt INVALID EIU OPERATION SELECTED –
PLEASE TRY AGAIN! will appear. If NOT USING PROKEES! is selected, 9 CHAR VMN ID
ENTRY RQD! (or 8 CHAR VVI ENTRY RQD!) must be selected.
PIN (Prokee
®
Internal Number) is not user selectable. It is a number generated by the
FuelMaster
®
software.
5. PIN is only available for use when using Prokee
®
s:
USAGE - <SPACE>=CHANGE VALUE, <ENTER>=NEXT FIELD, <ESC>=EXIT
----------------------------------------------------------------------------------------------------------
EIU SETUP FOR SAT#1:
GATE MASTER
USING PROKEES!
PIN ENTRY REQUIRED!
NOTE
A 9 CHAR VMN ID ENTRY RQD! means User IDs with up to 9 characters may be used. As few
as 1 character may be used. An ID entry of 4 will appear in the software database as 000000004.
If a VVI system is in use, the following prompt will show 8 CHAR VVI ENTRY RQD!, and a
Vehicle ID entry of 4 will appear in the software database as 00000004.
6. Press Enter:
USAGE - <SPACE>=CHANGE VALUE, <ENTER>=NEXT FIELD, <ESC>=EXIT
----------------------------------------------------------------------------------------------------------
EIU SETUP FOR SAT#1:
GATE MASTER
USING PROKEES!
PIN ENTRY REQUIRED!
9 CHAR VMN ID ENTRY RQD!
7. Pressing the space bar will change 9 CHAR VMN ENTRY RQD! to ID ENTRY NOT RQD!. Press
Enter:
USAGE - <SPACE>=CHANGE VALUE, <ENTER>=NEXT FIELD, <ESC>=EXIT
----------------------------------------------------------------------------------------------------------
EIU SETUP FOR SAT#1:
GATE MASTER
USING PROKEES!
285