Brocade Fabric OS Message Reference guide v6.2.0 (53-1001157-01, April 2009)
92 Fabric OS Message Reference
53-1001157-01
CONF-1021
13
CONF-1021
Message <timestamp>, [CONF-1021], <sequence-number>,, INFO, <system-name>, configUpload
not permitted <AD Number if AD is configured on the system>.
Probable Cause Indicates a configUpload operation is not permitted. There are many possible causes.
Recommended
Action
Check the error log, correct the error and rerun configupload.
Severity INFO
CONF-1022
Message <timestamp>, [CONF-1022], <sequence-number>,, INFO, <system-name>, Downloading
configuration without disabling the switch was unsuccessful.
Probable Cause Indicates an attempt to download the configuration without disabling the switch was unsuccessful
because there are one or more parameters that require the switch to be disabled.
Recommended
Action
Disable the switch and try to download the configuration.
Severity INFO
CONF-1030
Message <timestamp>, [CONF-1030], <sequence-number>,, WARNING, <system-name>,
Configuration database full, data not committed (key:<Key of failed configuration
data>.
Probable Cause Indicates that the previous configuration commands have resulted in a database full condition.
Configuration changes associated with specified key have not been applied.
Recommended
Action
Use configure and various other commands to erase configuration parameters no longer needed.
As a last resort, execute configDefault and reconfigure the system.
Severity INFO