Operating instructions
CAUTION: Hot plug is not currently supported by the operating systems. Do not
press switches
or on the hot-swap board. Pressing these
switches can result in the loss of data.
Complete the following procedure to add or remove a PCI option module.
1. Turn off the system power.
2. Unscrew captive screw
.
3. Press in latch button
and open the latch .
4. When replacing a PCI module, remove the bad module by pulling straight
out.
5. When adding a PCI option module into an unused slot, remove the blank
bulkhead
.
6. Install the new PCI option module
.
7. Screw in captive screw
.
8. Close latch
.
Close all latches before powering up the system. If the latch is open on either
slot 3 (Hose 3/Slot ID 2) or slot 4 (Hose 3/Slot ID 1), both slots will run at 33
Mhz.
Verification
1. Turn on power to the system.
2. At the P00>>> prompt, enter the SRM show config command. Examine
the PCI bus information in the display to make sure that the new option is
listed.
3. If you installed a bootable device, enter the SRM show device command to
determine the device name.
4-26 DS25 Owner’s Guide