Service manual

Power System 4-11
Figure 4-6 Worst-Case -EB & -EC Cabinet Power Configuration
StorageWorks StorageWorks
System Drawer
System Drawer
System Drawer
System Drawer
Fan
Tray
10A
10A
10A
30A
10A
10A
10A
0.38 Arms
0.38 Arms
0.38 Arms
0.38 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
1.83 Arms
0.5 Arms
7.8 Arms
8.1 Arms
8.1 Arms
200 - 240 Vrms
24.0 Arms
AC Distribution Box
Power Strips
PKW0406A -95
Total Power Available 4800 VA
Single Drawer 1100 VA
Single StorageWorks Shelf 150 VA
System Fan Tray 100 VA
Outlets 18 IEC 320 max. (3 power strips)
Site Grounding Leakage current exceeds 3.5 mAms.
Power Strip One system drawer per power strip.
In four-system drawer configuration, fourth
drawer should have its three power cords
distributed among the three power strips.