must allow 5,350 sq cm (830 square inches) of hole evenly distributed from top to
bottom to permit adequate airflow (equivalent to the required 64 percent open area for
ventilation).
Side: The clearance between the installed rack component and the side panels of the
rack must be a minimum of 7 cm (2.75 inches)
CAUTION:
Always use blanking panels to fill all remaining empty front panel U-spaces in
the rack. This arrangement ensures proper airflow. Using a rack without blanking
panels results in improper cooling that can lead to thermal damage.
HP ProLiant DL160 G6 models have fixed rails which provide support for racks with
round mounting holes and tool-free support for racks with square mounting holes
(including Compaq/HP 7000, 9000, 10000 and HP series), with an adjustment range of
24" - 36"
NOTE:
For additional information regarding Rack Cabinets and Telco Rack support,
please see the following URL:
www.hp.com/go/rackandpower
.
HP USB and SD Options
HP USB-P/S2 Mouse
DC369A
HP Keyboard (USB) standard 2004
DT528A#ABA
HP Internal USB Cable G6 Kit
NOTE:
In order to connect a USB device internally, the internal USB Cable G6 Kit
(536769-B21) must be used.
536769-B21
HP Care Pack Services
Hardware Services 4-Hour On-site Service
HP 3 year 4 hour 13x5 ProLiant DL14x and DL16x Hardware Support
U9509E
HP 3 year 4 hour 24x7 ProLiant DL14x and DL16x Hardware Support
U9510E
Hardware Services
HP 3 year Next business day ProLiant DL14x and DL16x Hardware Support
U9508E
HP Install ProLiant DL14x and DL16x Service
U9520E
NOTE:
For more information, customer/resellers can contact:
http://www.hp.com/services/carepack
QuickSpecs
HP ProLiant DL160 Generation 6 (G6)
Additional Options
DA - 13247 Worldwide — Version 59 — September 24, 2012
Page 35