AC power is distributed to the rack through a dual Power Distribution Unit (PDU) assembly mounted at the
bottom rear of the rack. The characteristics of the fully-re d und a nt rack power conguration are as follows:
Each PDU is connected to a separate circuit breaker-protected, 30–A AC site power source
(220–240 VAC ±1
0%, 50 or 60–Hz, ±5%). Figure 30 illustrates the compatible 60–Hz and
50–Hz wall receptacles.
CXO7549
A
NEMA L6-30R re
ceptacle, 3 -wire, 30-A, 60-Hz
CXO5409
B
IEC 309 receptacle, 3–wire, 30–A, 50–Hz
Figure 30 60
Hz and 50–Hz wall receptacles
The standard power conguration for any Enterprise Virtual Array rack is the fully r edundant
conguration. Implementing this con guration requires:
Two separate circuit breaker-protected, 30–A site power sources with a compatible wall
receptacl
e(seeFigure 30).
One dual PDU assembly. Each PDU connects to a different wall receptacle.
Six Power D istribution Modules (PDM) per rack. Three PDMs mount vertically on each side
of the rac
k. Each set of PDMs connects to a different PDU.
The d rive enclosure power supplies o n the left (PS 1) connect to the PDMs on the left with a
gray, 66 cm (26 in) power cord.
The drive
enclosurepowersuppliesontheright(PS2)connecttothePDMsontherightwitha
black, 66 cm (26 in) power cord.
The upper controller connects to a PDM on the left with a gray, 152 cm (60 in) power cord.
•Thelowe
r controller connects to a PDM on the right with a black, 66 cm (26 in) power cord.
NOTE:
Drive enclosures, when purchased separately, include one 50 cm black cable and one 50 cm gray cable.
The conguration p rovides complete power redundancy and elim i nates all single points of failure for
both the AC and DC power distribution.
PDUs
Each Enterprise Virtual Array rack has either a 50– or 60–Hz, dual PDU mounted at the bottom rear
of the rack. The 228481–002/228481–003 PDU placement is back-to-back, plugs facing down, with
switches on top.
The standard 50–Hz PDU cable has a n IEC 309, 3–wire, 30–A, 50–Hz connector.
The standard 60–Hz PDU cable has a NEMA L6–30P, 3–wire, 30–A, 60–Hz connector.
If these connectors are not compatible with the site power distribution, you must replace the PDU power
cord cable connector.