5. Verify that the am bient temperature range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as
necessary.
6. Observe the EMU to ensure the error is corrected.
7. If un able to correct the problem, contact your authorized service representative.
0.4.en.03 NON
CRITICAL condition—Low temperature
This condition report indicates that an element temperature is approaching, but has not reached, the low
temperature CRITICAL threshold. Continued operation under these conditions may result in a CRITICAL
condition. T
his condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Verify that the ambient temperature range is +10 °C to +35 °C (+ 50 °F to +95 °F). Adjust as
necessary.
3. Observe the EMU to ensure the error is corrected.
4. If the a mbient temperature is correct a nd the problem persists, contact your Authorized Service
Represent
ative.
0.4.en.04 CRITICAL condition—Low temperature
This condition report indicates that an element temperature has reached the low temperature CRITICAL
threshold. HP recommends correcting this error to prevent affecting other elements. This condition
report remains active until the problem is corrected.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Verify that the ambient temperature range is +10 °C to +35 °C (+ 50 °F to +95 °F). Adjust as
necessary.
3. Observe the EMU to ensure the error is corrected.
4. If the ambient temperature is c orrect and the problem persists, contact your authorized service
representative.
0.4.en.05 UNRECOVERABLE condition—High temperature
This condition report indicates that the E MU has evaluated the temperature of the three temperature
groups
(EMU, disk drives, a nd power supplies), and d etermined that the average temperature of two
of the t
hree groups exceeds the critical level (use HP Command View EVA to view the tempera ture
thresholds). Under these conditions the EMU starts a timer that will automatically shut down the enclosure
in seven minutes unless you c orrect the problem. Enclosure shutdown is imminent!
CAUTI
ON:
An aut
omatic shutdown and possible data corruption may result if the procedure below i s not performed
immediately
.
Complete the following procedure to correct this problem.
1. Ensure that all disk drives, I/O modules, and power supply elements are fully seated.
2. Ensure that all blowers are operating properly.
3. Verify that the ambient temperature range is +10 °C to +35 °C (+ 50 °F to +95 °F). Adjust as
necessary.
Enterprise Virtual Array 3000/5000 user guide