0.1.en.04 CRITICAL condition—Loop a drive link rate incorrect
The d rive is capable of operating at the loop link rate b ut is running at a different rate. For example, the
drive is operat
ing at 1 Gbps, and the loop is operating at 2 Gbps. Only when the drive is operating at
the Fibre Chann
el link rate established by the I/O mod ule can this drive transfer data.
This error remains active until the problem is corrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the c ondition report.
2. Remove and rep
lacethedriveintheenclosure.
3. Observe the drive status indicators to ensure the drive is operational.
4. Observe the EMU to ensure the error is corrected.
5. If removing a
nd replacing the drive did not correct the problem, replace the drive.
6. Observe the drive status indicators to ensure the drive is operational.
7. Observe the EMU to ensure the error is corrected.
8. If unable to
correct the problem, contact your authorized service representative.
0.1.en.05 CRITICAL condition—Loop b drive link rate incorrect
The d rive is capable of operating at the loop link rate b ut is running at a different rate. For example, the
drive is operating at 1 Gbps, and the loop is operating at 2 Gbps. Only when the drive is o perating at
the Fibre Channel link rate established by the I/O module can this drive transfer data.
This error remains active until the problem is corrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the c ondition report.
2. Removeandreplacethedriveintheenclosure.
3. Observe the drive status indicators to ensure the drive is operational.
4. Observe the EMU to ensure the error is corrected.
5. If removing and replacing the drive did not correct the problem, replace the drive.
6. Observe the drive status indicators to ensure the drive is operational.
7. Observe the EMU to ensure the error is corrected.
8. If unable to correct the problem, contact your authorized service representative.
Power supply conditions
The format of a power supply condition report is 0.2.en.ec,where:
• 0.2. is the power supply element type number
• en. is
the two-character power supply element number
• ec is the error code
Figure 41 shows the location of power supply 1 and power supply 2.
118
EMU-generated condition reports