Manual

Table 44 10000-Series Enterp rise 42U Rack Physical Dimensions
Conguration He ig ht i n / mm Width i n / mm Depth in / m m Max Wt lbs / kg
Enterprise 2C6D
78.75 / 2000 .0 23.7 / 600 39.3 / 1000 918 / 416
Enterprise 2C12D
78.75 / 2000 .0 23.7 / 600 39.3 / 1000 1350 / 612
Enterprise 0C6
D
78.75 / 2000 .0 23.7 / 600 39.3 / 1000 818 / 371
Enterprise 0C12D
78.75 / 2000 .0 23.7 / 600 39.3 / 1000 1250 / 567
Table 45 10000-Series Enterprise 42U Rack Shipping Dimensions
Congurations Height in / mm Width in / mm Depth in / mm
Max Wt
(packaging)
lbs / kg
Enterprise 2C
6D
86.22 / 2190 32.0 / 813 48.0 / 1220 1111 / 504
Enterprise 2C12D
86.22 / 2190 32.0 / 813 48.0 / 1220 1543 / 700
Enterprise 0C6D
86.22 / 2190 32.0 / 813 48.0 / 1220 1011 / 459
Enterprise 0C
12D
86.22 / 2190 32.0 / 813 48.0 / 1220 1443 / 654
Environmental specications
To ensure op timum product operation, you must maintain the operational environmental specications
listed in Table 46. The ambient temperature (the enclosure air intake o r room temperature) is especially
critical.
Table 46 Environmental operating spec ications
Ambient temperature:+1Cto+3C(+5Fto+9F)withanaveragerateofchangeof1°C/hour
maximum and a step change of 3 °C or less. Maintaining the optimum ambient temperature within the
specied range ensures that th e internal operating temperatures support the drive manufacturer’s MTBF
specications.
Relative humidity: 40% to 60% (noncondensing) with a step change of 10% or less (noncondensing).
Air quality: Not to exceed a maximum of 500,000 particles, 0.5 micron or larger, per cubic foot of air.
Heat dissipation: 12,708 BTUs per hour.
When shipping, or placing this product in short term storage, HP recommends m aintaining the
environme
ntal conditions listed in Table 47.
Table 47 Environmental shipping or short term storage specications
Ambient tem perature: –40 °C to +66 °C (–40 °F to +151 °F)
Relative humidity: 10% to 80% (nonc ondensing)
Altitude:
below 15,240 m (50,000 ft)
Power specications
Table 48 denes the AC power specications for the Enterprise Virtual Array PDUs, PDMs, drive enclosure
power supplies, and controller enclosure power supplies.
112
Regulatory notices and specications