Instruction Manual

1. Record all six characters of the condition report.
2. Reset the EMU.
3. Observe the EMU to ensure the error does not recur within the rst minute.
4. If the error does recur, contact your HP authorized service representative. The EMU is inoperative
andmustbereplacedassoonaspossible.
0.7.01.19 UNRECOVERABLE condition—EMU ESI driver failure
The EMU has detected a n internal hardware problem. This condition report remains active until the
problem is cor
rected.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Reset the EMU.
3. Observe the
EMU to ensure the error does not recur within the rst minute.
4. If the error does recur, contact your HP authorized service representative. The EMU is inoperative
andmustbereplacedassoonaspossible.
Transceiver conditions
The format of a transceiver condition report is 0.F.en.ec,where:
0.F. is the transceiver element type number
en. is the two-character transceiver element number (see Figure 63)
ec is the error co d e
CXO7954
A
3 1
4 2
Figure 63 Transceiver element numbering
1. Transceiver 01
2. Transceiver 02
3. Transceiver 03
4. Transceiver 04
0.F.en.01CRITICALConditionTransceiverIncompatibility
The transceivers on this link are not the same type or they are incompatible with the I/O module. This
error prevents the controller from establishing a link with the enclosure drives and eliminates the enclosure
dual-
loop capability. This error remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service representative.
148
EMU generated condition reports