Instruction Manual

To correct this problem, record all six characters of the condition report, then contact your authorized
service representativ e.
0.3.en.03 UNRECOVERABLE condition—Blower failure
A blower has stopped. The operational blower now operates at high speed and is a single point of
failure. This condition report remains active until the problem is corrected.
To correct this
problem, record all six characters of the condition report, then contact your authorized
service representativ e.
0.3.en.04 UNRECOVERABLE condition—Blower internal
A power supply reported an internal blower error that could affect enclosure cooling and cause an
element to fail. HP recommends correcting the problem before the blower fails. This condition report
remains active until the problem is corrected.
To correct this problem, record all six characters of the condition report, then contact your HP authorized
service representativ e.
0.3.en.05 NONCRITICAL condition—Blower missing
A blower has been removed or is improperly installed. Even though the blower aps close to maintain
the proper air ow, the reduced cooling capability can cause overheating, c ausing an element to fail.
This condition report remains active until the problem is corrected.
To correct t
his problem, record all six characters of the condition report, then contact your HP authorized
service representativ e.
0.3.en.06 UNRECOV ERABLE condition—No blowers installed
NOTE:
IMPORTANT
When this condition exists there will be two error messages.
The rst message will be 0.3.en.05 and will identify the rst blower.
The second message will be 0.3.en.06 and will identify the second blower.
TheEMUcannotdetectanyinstalledblowers. Shutdown is imminent! The EMU will shut down the
enclosure in seven minutes unless you correct the problem. This condition report remains active until you
correct the problem or the EMU shuts down the power supplies, whichever occurs rst.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Use the controller shutdown procedure to shut down the controllers.
3. Contact your authorized service representative.
CAUTION:
An automatic shutdown and possible data corruption may result if the blower is removed before
a r eplacement is available.
Temperature conditions
The format of a temperature condition report is 0.4.en.ec,where:
0.4. is temperature sensor element t ype
Enterprise Virtual Array 3000/5000 user guide (VCS 3.110)
141