Instruction Manual
ThesiteACinputvoltageisroutedtoeachPDUmountedintherack.EachPDUdistributesACthrough
ten receptacles directly to the storage system components.
• PDUs 1 and 3 (optional) are mounted on the left side of the cabinet. Grey power cords connect
these PDUs to the number 1 drive enclosure power supplies and to the controller enclosures.
• PDUs 2 and 4 (optional) are mounted on the right side of the cabinet. Black power cords connect
these PDUs to the number 2 drive enclosure power supplies and to the controller enclosures.
Moving and stabilizing a rack
WARNING!
The physical size and weight of the rack requires a minimum of two people to move. If one person tries
to move the ra
ck, injury may occur.
To ensure stab
ilityoftherack,alwayspushonthelowerhalfoftherack. Beespeciallycarefulwhen
moving the rack over any bump (for example: door sills, ramp edges, carpet edges, or elevator
openings). When the rack is moved over a bump, there is a potential for it to tip over.
Moving the rack requires a clear, uncarpeted pathway that is at least 80 cm (31.5 in) wide for the
60.3 cm (23.7 in) wide, 42U rack. A vertical clearance of 203.2 cm (80 in) should ensure suf ficient
clearance for the 200 cm (78.7 in) high, 42U rack.
CAUTION:
Ensurethatnoverticalorhorizontalrestrictionsexistthatwouldpreventrackmovementwithout
damaging the rack.
Make sure that all four leveler feet are in the fully raised position. This process will ensure that the casters
support the rack weight and the feet do no impede movement.
Each 10000-Series rack requires an area 600 mm (23.62 in) wide and 1000 mm (39.37 in) d eep
(see Figure 56).
112
Storage system hardware components