Service and Maintain
Periodic maintenance 64
Component to be inspected Task Frequency Capable Party
Humidifier drains
Put the humidifier in system flush
mode and inspect drain flow and
water supply flow. Inspect, clean,
and/or replace as necessary.
Quarterly Qualified personnel
—
Inspect for any internal or external
water leaks, repair or replace
leaking components.
Quarterly
Qualified personnel
—
Using LLS, verify proper cylinder
operation. Inspect the cylinder for
blackened areas and, if present,
check the condition of the
electrodes. If necessary, replace
the cylinder.
Quarterly Qualified personnel
—
Replace the cylinder. Annually Qualified personnel
ECS
Component to be inspected Task Frequency Capable Party
Full system functional check
Operational check of all system
components
Quarterly Qualified personnel
—
Check and clear alarm log Quarterly Qualified personnel
—
Inspect and test ECS battery
backup system
Every 2 years Qualified personnel
Electrical
Maintenance of the electrical components might require the following:
• Expose personnel to high voltage.
• Allow personnel to come into direct contact with high voltage.
• Power down the POD during the execution of the maintenance item.
You must explicitly state and acknowledge if a POD power down will be possible. If a power down is not
possible, LLS inspections will be conducted and further action will be taken at your discretion.
Component to be inspected Task Frequency Capable Party
Electrical connections
Use LLS to check for major
electrical connections (torque
marks, sizzle, and acrid odor):
•
Main/House Power Feeds
•
Busway End Feeds, Drop
Boxes (including cables and
cord caps)
•
Electrical panels, breakers,
and disconnects
•
480/415 VAC transformer
Quarterly
Licensed electrician