QuickSpecs
Additional Interface
Cards
8
8 -14 8 -14
Typical Electrical Characteristics by Configuration
Typical Electrical Characteristics by ConfigurationTypical Electrical Characteristics by Configuration
Typical Electrical Characteristics by Configuration
AC input power
200 240 VAC, 50/60 Hz 200 240 VAC, 50/60 Hz 200 240 VAC, 50/60 Hz
Typical Input Power
(watts)
dissipation Itanium 2
(watts)
5,900
4 cells, 32 GB, 4 I/O
chassis with 6 PCI each
9,800
8 cells, 32 GB, 4 I/O
chassis with
6 PCI each
19,600
16 cells, 32 GB, 4 I/O
chassis with
6 PCI each
Typical power dissipation
mx2 (watts)
5,730 9,490
18,980
Typical 3 Phase 4Wire
Current requirements at
200V 240V
17A / Phase 29A / Phase
Two Cabinets 29A /
Phase
Typical 3 Phase 5Wire
Current requirements at
200V 240V
10A / Phase 17A / Phase
Two Cabinets 17A /
Phase
Maximum Electrical Characteristics
Maximum Electrical CharacteristicsMaximum Electrical Characteristics
Maximum Electrical Characteristics
Maximum Input Power
(VA)
Cabinet Marked Electrical
8,200
12,196 24,392
AC input power-Option
7: 3 phase 5 wire input
200 240 VAC phase to neutral, 5 wire, 50/60 Hz
AC input power-Option
6: 3 phase 4 wire input
200 240 VAC phase to phase, 4 wire, 50/60 Hz
Maximum Current requirements at 220V 240V:
Option 7: 3 phase 5 wire
input
24 A/Phase 24 A/Phase 24 A/Phase
Option 6: 3 phase 4 wire
input
44 A/Phase 44 A/Phase 44 A/Phase
Required Power
Receptacle-
Option 6: IEC Compliant 4 Wire 60A 250V Ph-Ph
Option 5: IEC Compliant 5 Wire 32A 480VPh-Ph
Heat Characteristics
Heat CharacteristicsHeat Characteristics
Heat Characteristics
Maximum Heat
dissipation (BTUs/hour)
28,969 41,614 83,288
Typical Heat dissipation
(BTUs/hour)
20,131 33,439 66,877
Site Preparation
Site PreparationSite Preparation
Site Preparation
Site planning and
installation included
Yes Yes Yes
Depth (mm / inches)
1,220 / 48.1 1,220 / 48.1 1,220 / 48.1
Width (mm / inches)
762 / 30 762 / 30
1,524 / 60
Height (mm / inches)
1,960 / 77.2 1,960 / 77.2 1,960 / 77.2
Weight (Kg / lbs)
500 / 1,123 598 / 1,343
1,196 / 2,685
QuickSpecs
HP Integrity Superdome Servers 16- processor, 32-
HP Integrity Superdome Servers 16- processor, 32-HP Integrity Superdome Servers 16- processor, 32-
HP Integrity Superdome Servers 16- processor, 32-
processor, and 64- processor Systems
processor, and 64- processor Systemsprocessor, and 64- processor Systems
processor, and 64- processor Systems
Technical Specifications
DA - 11717 Worldwide — Version 35 — December 6, 2006
Page 63