User's Manual

6
HBM: Business Document
Important
Even if the unit is installed correctly, the zero point adjustment made at the
factory can shift by up to approx. 0.5% of the characteristic value. If this value
is exceeded, we advise you to check the mounting conditions. If the residual
zero offset when the unit is removed is greater than 1% of the sensitivity,
please send the transducer back to the Darmstadt factory for testing.
5.2 Conditions on site
The special torque flange must be protected against coarse dirt particles,
dust, oil, solvents and humidity.
There is wide ranging compensation for the effects of temperature on the
output and zero signals of the transducer (see Chapter 13, "Specifications"). If
there are no static temperature ratios, for example, because of the
temperature differences between the measuring body and the flange, the
values given in the specifications can be exceeded. In this case, ensure static
temperature ratios by cooling or heating, depending on the application. As an
alternative, check if thermal decoupling is possible, e.g. by means of heat
radiating elements such as multiple disc couplings.
5.3 Installation orientation
The torque flange can be installed with any orientation.
With clockwise torque, when using the voltage output mode a positive output
signal (0 V…+10 V) or when using the frequency output mode an output
frequency of 10 kHz 15 kHz is present on the output (corresponding zero to
nominal torque load).
5.4 Installation options
There are basically two options for mounting the special torque flange: with or
without dismantling the antenna ring. We recommend mounting as described
in Chapter 5.4.1.
If mounting in accordance with Chapter 5.4.1 is not possible (e.g. in the case
of subsequent stator replacement), you will have to dismantle the antenna
ring. It is essential in this case to comply with the notes on
assembling the
antenna segments (see Chapter 5.4.2).