Service Manual

12
3. Undercounter and Work Top: Freezer
Freezer Sequence Flow Chart
Legend:
Comp-compressor
ConFM-condenser fan motor
CTh-cabinet thermistor
DH-defrost heater
DT-defrost timer
DTh-defrost thermistor
EvapFM-evaporator fan motor
MH-mullion heater
PH-perimeter heater
1. Startup/Cool Down
2. Cool Down Achieved
Comp energized
ConFM energized
EvapFM energized
MH energized
PH energized
CTh in control
Setpoint
Achieved
CTh warms
above
setpoint
3. Defrost
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
5. Defrost Termination
DTh in control
2-min. Comp off
timer starts
2-min. Comp on
timer starts
6-hr. or 8-hr. DT starts
Defrost Termination:
50°F (°10C) achieved or
1 hr. backup defrost timer
terminated.
8-hr. DT terminates
Evap. temp. below 41°F (5°C)
5-min. min. DT starts
60-min. max. DT starts
DH energized
Comp de-energized
ConFM de-energized
EvapFM de-energized
MH de-energized
PH de-energized
Defrost Initiation:
Time/Temp achieved.
Note: Delays
a) 2-min. minimum Comp on timer starts when Comp energizes.
b) 2-min. minimum Comp off timer starts when Comp de-energizes.
c) 5-min. minimum defrost time.
d) 1-hr. maximum defrost time.
e) DOT (drip off time) 3-min. Comp/ConFM delay timer starts when defrost termination temperature is met (drip off time (DOT)).
f) FDD (fan delay after defrost) EvapFM starts once 7-min. EvapFM delay timer terminates or DTh reaches 25°F (-4°C).
*
DH de-energized
8-hr. DT starts
After DOT Delay:
Comp energized
ConFM energized
MH energized
PH energized
After FDD
EvapFM energized
*
*
Defrost
Terminated
8-hr. DT terminates
Evap. temp. below 41°F (5°C)
Power on
Red LED On
(5 sec. Delay)
Red LED off
Green LED Flashes
If Red LED ashes,
check CTh or DTh