Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Timer (S4 dip switch 1 & 2)
- 3. Pump-Out Timer/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist Duration) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Control Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- 11. Minimum Harvest Time (S5 dip switch 4)
- 12. Anti-Slush (S5 dip switch 5)
- IV. Refrigeration Circuit and Component Service Information
- VII. Disposal
- VIII. Technical Information
10
F/S open
F/S check
• Minimum freeze time: 5 min.
• Maximum freeze time: freeze timer setting
(S4 dip switch 9 & 10)
Components Energized when the Control Switch is in the "SERVICE" Position
When in the "SERVICE" position, the control switch supplies power to the service switch and the icemaker is in service mode.
The service switch has three positions: "DRAIN," "CIRC." and "WASH." See the information below for details of each function.
DRAIN
Power is supplied to the pump motor and drain valve. This drains the water tank.
CIRC.
Power is supplied to the pump motor only. This operation can be used to circulate cleaner
and sanitizer over the outside surface of the evaporator for extended periods of time.
WASH
Power is supplied to the pump motor and wash valve. This operation is used to circulate
cleaner and sanitizer over both the inside and outside surfaces of the evaporator.
4. Pump-Out Cycle
1. 1-Minute
Fill Cycle
2. Harvest Cycle
3. Freeze Cycle
Cycle
Steps
WV energized
F/S closed
WV continues
Comp energized
FMRs energized
HGVs energized
Thermistor temperature
reaches 48°F (9°C)
(3.9 kΩ or less)
Harvest timer starts.
F/S open
Comp continues
FMRs continue
PM continues
LLVs energized
HGVs de-energized
Comp continues
FMRs continue
HGVs energized
DV energized
PM de-energizes for 2 sec.,
then energized for 10/20 sec.
LLVs de-energized
F/S check
• WV time: 6 min. or the length of harvest minus
HPT settings (S4 dip switch 6), whichever is
shorter.
• Maximum harvest time: 20 min.
Thermistor
in control
1 to 3-min. timer in control
(S4 dip switch 1 & 2)
Startup
begins
here after
5-sec. delay
If F/S is open, Comp and FMRs de-energize and cycle returns to 1-minute ll cycle
• Factory set forevery
10th cycle.
(S4 dip switch 5)
• Pump motor stops for
2 sec., then energized
for 10/20 sec.
(S4 dip switch 3 & 4)
PM energized
WV de-energized
HarvestPump Timer
Legend:
BC-bin control
Comp-compressor
DV-drain valve
FMRs-fan motors-remote
F/S-oat switch
HGVs-hot gas valves (KMS and SRK)
LLVs-liquid line valves (KMS and SRK)
PM-pump motor
WV-inlet water valve
Operation Flow Chart
Anti-Slush
Thermistor
temperature
drops to 36°F
(2.2°C) (5.8 kΩ
or more).
PM de-energizes
for 10 sec.
50 sec.
FS in control
FS closed
5-min. minimum
freeze timer in
control
FS opens or freeze
timer terminates
When freeze time differential exceeded,
freeze-time correction cycle starts.
See "II.A.3. Freeze-Time Correction Chart."
II. Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Chart
1. Operation Flow Chart