Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagrams
- II. Sequence of Operation and Service Diagnosis
- III. Settings and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Time (S4 dip switch 1 & 2)
- 3. Pump-Out Time/Harvest Time During Pump-Out (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5)
- 5. Harvest Pump Time (Harvest Assist Duration) (S4 dip switch 6)
- 6. Harvest Pump Time (Harvest Assist)/Freeze-Time Correction (S4 dip switch 7)
- 7. Factory Use (S4 dip switch 8)
- 8. Freeze Timer (S4 dip switch 9 & 10)
- 9. Float Switch Control Selector (S5 dip switch 1)
- 10. Refill Counter (S5 dip switch 2 and 3)
- 11. Minimum Harvest Time (S5 dip switch 4)
- 12. Anti-Slush (S5 dip switch 5)
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
32
I. Diagnostic Tables
Before consulting the diagnostic tables, check for correct installation, proper voltage per
nameplate, and adequate water pressure (10 to 113 PSIG). Check control board using the
steps in "II.D. Control Board Check."
1. No Ice Production
No Ice Production - Possible Cause
1. Power Supply a) Off, blown fuse, or tripped breaker.
b) Not within specications.
2. Main Transformer
(3 phase SRK)
(208-230VAC/115VAC)
a) Voltage tap switch not set to proper voltage.
b) No neutral. White (W) wire to ground 0VAC. (White (W) wire to
ground should be 60VAC).
3. Water Supply a) Water supply off or improper water pressure.
b) External water lters clogged.
4. Fuse (SRK Control Box) a) Blown.
5. High-Pressure Switch (SRK) a) Dirty condenser.
b) Condensing unit fan(s) not operating.
c) Headmaster (C.P.R.) open.
d) Refrigerant overcharged.
e) Bad contacts.
f) Refrigerant lines or components plugged.
6. Discharge Line Thermostat
(SRK)
a) Ambient temperature too warm.
b) Compressor or compressor components defective.
c) Defective.
d) Hot gas valve(s) open.
e) Dirty condenser.
f) Condensing unit fan(s) not operating.
7. Wire Harness
(From SRK to KMS)
a) Disconnected or loose connection.
8. Fuse (KMS Control Box) a) Blown.
9. Control Switch a) In "SERVICE" or "OFF" position.
b) Bad contacts.
10. Control Transformer
(115VAC/10.5VAC)
a) Coil winding open or shorted.
11. Control Board
See "II.D. Control Board Check"
a) In alarm.
b) Yellow "BC OPEN" LED on: Bin full.
c) Defective.
12. Bin Control
See "II.E. Bin Control Check"
a) Tripped with bin lled with ice.
b) Actuator does not move freely.
c) Defective.
13. Fill/Rell (WV1) or
Harvest Water Valve (WV2)
a) Screen or orice clogged.
b) Coil winding open.
c) Water valve open in freeze cycle.