Service Manual
Table Of Contents
- Important Safety Information
- I. Construction and Water/Refrigeration Circuit Diagram
- II. Sequence of Operation and Service Diagnosis
- III. Controls and Adjustments
- A. Control Board Layout
- B. LED Lights and Audible Alarm Safeties
- C. Settings and Adjustments
- 1. Default Dip Switch Settings
- 2. Harvest Timer (S4 dip switch 1 & 2)
- 3. Pump-Out Timer (S4 dip switch 3 & 4)
- 4. Pump-Out Frequency Control (S4 dip switch 5 & 6)
- 5. Harvest Pump Timer Operation (S4 dip switch 7)
- 6. Factory Use (S4 dip switch 8)
- 7. Freeze Timer (S4 dip switch 9 & 10)
- 8. Float Switch Selector (S5 dip switch 1)
- 9. Refill Counter (S5 dip switch 2, 3, and 5), Program Selector (4)
- D. Switches
- IV. Refrigeration Circuit and Component Service Information
- V. Maintenance
- VI. Preparing the Appliance for Periods of Non-Use
- VII. Disposal
- VIII. Technical Information
13
"G" Control Board without Harvest Pump Timer Operation Flow Chart
1. 1-Minute Fill
Cycle
2. Harvest Cycle 3. Freeze Cycle
4. Pump-Out Cycle
Cycle
Steps
WV Energized
FS open
FS closed
Comp energized
FMR energized
HGV energized
WV energized
LLV de-energized
Thermistor temperature
reaches 48°F (9°C)
(3.9kΩ or less) Harvest
timer starts (1 to 3 min.).
FS open
Comp continues
FMR continues
FM energized
LLV energized
PM energized
HGV de-energized
WV de-energized
FS closed
Comp continues
FMR continues
HGV energized
PM de-energizes for 2 sec.,
then DV and PM energize
for 10/20 sec.
FM de-energized
LLV de-energized
FS Check
FS Check
• Maximum inlet water valve time: 6 minutes
• Maximum harvest time: 20 minutes
Thermistor in
control
1 to 3 min. harvest
timer in control
(S4 dip switch 1 & 2)
• Min. freeze time: 5 min.
• Max. freeze time: freeze timer
setting
(S4 dip switch 9 & 10)
5 min. minimum
freeze timer in
control
FS in control
If FS is open, Comp stops and cycle returns to 1-min. ll.
Legend:
Comp–compressor
DV–drain valve
FM–fan motor
FMR–fan motor-remote
FS–oat switch
HGV–hot gas valve
LLV –liquid line valve
PM–pump motor
WV–inlet water valve
Components Energized when the Control Switch is in the "SERVICE" Position
When in the "SERVICE" position, the control switch supplies power to the service switch and the machine is in service mode.
The service switch has three positions: "DRAIN," "CIRCULATE" and "WASH." See the information below for details of each
function.
DRAIN
Power is supplied to the pump motor and drain valve. This drains the water tank.
CIRCULATE
Power is supplied to the pump motor only. This can be used to circulate cleaner over the
outside surface of the evaporator for extended periods of time.
WASH
Power is supplied to the pump motor and wash valve. This is used to circulate cleaner and
sanitizer over both the inside and outside surfaces of the evaporator.
II. Sequence of Operation and Service Diagnosis
A. Sequence of Operation Flow Chart
1. "G" Control Board without Harvest Pump Timer Operation
• Every 1, 2, 5, or 10
cycles
(S4 dip switch 5 & 6)
• Pump motor stops for
2 sec., then energizes
for 10/20 sec.
(S4 dip switch 3 & 4)
FS opens or
freeze timer
terminates
Startup
Shutdown and Restart See "II.A.3. Thermostatic and Mechanical Bin Control Shutdown Operation"